Product Overview
The N2XRH 2×10 mm² 0.6/1 kV power cable is designed for fixed installations requiring enhanced mechanical protection and high safety standards regarding fire performance and emission of corrosive gases. Built with copper conductors, XLPE insulation, round galvanized steel wire armour, and a halogen-free outer jacket, this cable ensures reliable power distribution in harsh industrial environments, infrastructure projects, and commercial buildings where personnel and equipment safety are critical.
Key Technical Specifications
- Conductor: Solid or stranded copper conductor
- Cross-Section: 2×10 mm²
- Rated Voltage: U0/U = 0.6/1 kV
- Insulation Material: XLPE (Cross-linked polyethylene)
- Armour: Round galvanized steel wire armour providing high mechanical strength
- Outer Sheath: Low Smoke Zero Halogen (LSZH / HFFR) compound
- Fire Performance / CPR: Eca classification
| Parameter | Specification |
| Cable Type | N2XRH |
| Number of Cores & Cross-Section | 2 x 10 mm² |
| Rated Voltage | 0.6/1 kV |
| Insulation | XLPE |
| Armouring | Galvanized Steel Wire |
| Sheath Material | LSZH (Halogen-Free) |
| CPR Rating | Eca |
Applications & Installation
N2XRH cables are suitable for indoor and outdoor installations, in cable ducts, underground, and in power-generating stations where mechanical damage is a risk. Due to its halogen-free and flame-retardant properties, it is extensively specified for environments with high concentrations of people and valuable assets, such as tunnels, hospitals, data centers, high-rise buildings, and industrial plants. The steel wire armour provides robust protection against external mechanical stresses during laying and operational lifecycles.
Standards & Compliance
Manufactured in strict accordance with recognized national and international electrical standards to guarantee complete operational reliability and compliance with global procurement requirements.
- Design Standards: TSEK 339, TS IEC 60502-1
- Flame Retardancy: IEC 60332-1-2
- Halogen-Free Properties: IEC 60754-1/2
- Smoke Density: IEC 61034-2